- Radeberger Str. 21
D - 01900 Großröhrsdorf / Germany - Phone +49 (0)35952 / 42 94 65
Fax +49 (0)35952 / 42 94 57
info∂dks-engineering.de
Dew Point
The Dew Point Sensor NP330- G
The Dew Point Sensor NP330- G  is a 4-20mA transmitter to measure absolute moisture in °C dew point (°C dp) in gases.
Due to a special manufacturing process it has a high media compatibility for use as online unit for the most diverse gases and gas mixtures for control, monitoring and quality assurance in gas treatment. Due to its wide measuring range the sensor is used for monitoring and control of freeze dryers and adsorption dryers.
The use of the NP330-G ensures the quality of air dryers in production processes and saves energy during drying.
technical data |
|
|
Measuring range Dewpoint: |
-80 °C dp - +20 °C dp |
|
Measuring range Temperature: |
-20 °C - +60 °C |
|
Measuring accuracy: |
± 2 °C dp |
|
Operating Pressure:: |
Vakuum bis 30 MPa |
|
Temperature Compensation: |
 available |
|
Operating Temperature: |
-20° C - +60° C |
|
Medium compatibility: |
ther most gases and gas mixtures |
|
Protective sleeve: |
Sinter guard filter, stainless steel 80 µm |
|
Operating voltage: |
18 – 28 V DC, ca. 30 – 70 mA |
|
Outputs: |
Current output 4-20 mA, max. BĂĽrde 1kOhm |
|
Connector: |
Circular connector, 7-pins, |
|
Protection: |
IP 65 |
|
Sample connecting thread: |
5/8 – 18 UNF, SW 22 mm |
|
Depht: |
50 mm |
|
High of housing: |
115 mm |
|
Housing diameter: |
60 mm |
|
Length: |
176 mm |
|
Mass: |
450 g |
|
Recalibration: |
Time intervals dependent on the employment an annual examination is recommended. |
Dew point switch typ NP 400
The dew point switch typ NP 400
is designed according to the same principle as the sensor above.
However, as a low cost unit, it is especially intended to monitor moisture in gases.
This is achieved by an electronic unit integrated in the sensor head and contains two adjustable outputs. A preset fixed switch point is triggered when the moisture is exceeded or falls short of it.
technical data |
|
|
Measured variable: |
Absolutfeuchtegehalt in Gasen |
|
Measuring range: |
Typ 1: -46 ... -14 °C TP |
|
Accuracy: |
± 3 °C TP |
|
Resolution: |
< 0,5 °C Tp |
|
2 switch points: |
variable |
|
switch hysteresis: |
variable in the range 1 ... 6 °C TP |
|
Time delay: |
variable in the range 1 ... 240 sec |
|
Circuit logic: |
active low (s the current dampness more largely than the adjusted threshold is the appropriate exit up Low-Pegel) |
|
Operating pressure: |
Vakuum to 30 MPa |
|
Operatingtemperature: |
0 ... +60 °C |
|
Operating voltage: |
24V DC +/- 15% , ca. 15 mA internal requirement |
|
Protection: |
IP 65 |
|
Output: |
operating voltage switches at exit, |
|
Connector: |
4 pin. Connector IEC 947-5-2 DIN/VDE 0660 |
|
Connection allocation: |
Pin 1: output 1 (green LED) |
|
Connecting Cable: |
Pin 1 - brown |
|
Sample connecting thread: |
1/2 ", SW 27 |
|
Depht: |
ca. 55 mm |
|
Lenght: |
ca. 138 mm |
|
Mass: |
ca. 105 g |
|
Rekalibration: |
Time intervals dependent on the employment an annual examination is recommended. |
For further information and ordering, please click on the link Contact on this page and request an offer.
You can also reach us over the phone 0049 35952 / 42 94 65.
We will be pleased to assist you.